- MOUNTING: 35mm DIN rail or surface mountable snap on
base
- SUPPLY RANGE: 7.5 TO 36Vdc
- SIGNAL OUTPUT: 4-20mA ( LOOP POWERED )**
CONNECTIONS: 30-12awg wire
- INPUT RANGE: 0-2400 mV
- INPUT TYPE: mV sensor
- INPUT IMPEDANCE: differential mode 0.1 G Ohms ||1 pf / common mode 5 G Ohms||10 pf
- INPUT EXCITATION: 5V (@2.5mA max)
- RESPONSE: < 10mS
- DIMENSIONS: 4.510 X 1.258 X 3.948 (height above
rail) LWH***
- * Loop termination resistor required when used
with voltage ADC
- ** 4-20mA signal uses a 2 wire connection.
Resistance transmitter output is connected in series, with supply and
measurement device.
- *** Mated connector adds additional 3/8” to height.
Use spare PLC 4-20mA inputs for mV sensor measurement, with the ROI-XMA mV sensor
transmitter. ROI-XMA mV transmitters allow the simple measurement of industry
standard sensors. Existing mV sensors can be connected to modern control systems.
The ROI-XMA transmitter can add mV sensor measurement to a PLC.
0-2400mV 4-20mA 2 wire loop powered transmitter 5Vdc sensor excitation 205USD